Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 12/6/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 repair the emergency lights, they did not come on, the bell worked 7/21/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Perform monthly fire service test and post a log in the machine room 7/21/2020
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection recovery pump in the elevator pit is not allowed per memo 006 from the state of Missouri, replace with bucket
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Recovery pump in the elevator pit for hydraulic oil not allowed per memo from the state, memo 006 (A17.1 8.6.5.5)