Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Perform monthly fire service test and post a log in the machine room 7/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Recovery pump in the elevator pit for hydraulic oil not allowed per memo from the state, memo 006 (A17.1 8.6.5.5)
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection recovery pump in the elevator pit is not allowed per memo 006 from the state of Missouri, replace with bucket
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 repair the emergency lights, they did not come on, the bell worked 7/21/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 12/6/2022