A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Perform monthly fire service test and post a log in the machine room 7/21/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x replace backup battery for emergency phone, it is dead and the phone will not work with the 110 volt power off 5/31/2022
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Remove escalator parts from machine room for the escalator that’s no longer installed at this location
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The emergency light and Bell did not work, replace emergency light battery
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 12/6/2022