Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)5 Pit ladder is rusted out at bottom. Repair or replace same and re-fasten to pit wall
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection incomplete, need to perform the following tests to complete inspection: Perform testing of emergency light, alarm and phone. Re-inspection required
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed. Perform required full load test within 90 days. 7/30/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light does not work when normal power is removed. 7/30/2021
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.2 x x Hydraulic supply piping in pit appears to be rusted through, began leaking during pressure testing. Red-tagged and removed from service. Needs to be repaired. Re-inspection required
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Fire extinguisher is outdated. 8/15/2018