MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Inspection incomplete, need to perform the following tests to complete inspection: Perform testing of emergency light, alarm and phone. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Pit ladder is rusted out at bottom. Repair or replace same and re-fasten to pit wall
|
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher is outdated.
|
8/15/2018
|
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.2
|
x
|
x
|
Hydraulic supply piping in pit appears to be rusted through, began leaking during pressure testing. Red-tagged and removed from service. Needs to be repaired. Re-inspection required
|
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light does not work when normal power is removed.
|
7/30/2021
|
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV is not sealed. Perform required full load test within 90 days.
|
7/30/2021
|