MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
3) All electrical wiring in the hoistway shall be enclosed or be in compliance with NFPA 70, top floor interlock cover missing. NEC 620.4 Ref: (A) 16
|
2/11/2021
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
|
|
2) Machine rooms and machinery spaces shall be enclosed throughout their height with fire-resistive enclosures as required by the building code. Openings created by the installation of plumbing lines from the renovation of the building have violated the fire rating.
|
2/7/2020
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
|
|
2) Machine rooms and machinery spaces shall be enclosed throughout their height with fire-resistive enclosures as required by the building code. Openings created by the installation of plumbing lines from the renovation of the building have violated the fire rating.
|
2/7/2020
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.2
|
|
|
1) Only machinery and equipment used in conjunction with the function or use of the elevator shall be permitted in the elevator machine room. Plumbing lines, water and drain lines, coming through floor from a renovation to the building must be removed or apply for a variance.
|
2/7/2020
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.2
|
|
|
1) Only machinery and equipment used in conjunction with the function or use of the elevator shall be permitted in the elevator machine room. Plumbing lines, water and drain lines, coming through floor from a renovation to the building must be enclosed or guarded so that any leaks that occur will not effect elevator equipment. As per the Elevator Safety Board, sent in a letter.
|
2/7/2020
|
A17.1-1996 : Elevators
|
3.3 - Top-of-car operating device
|
210.1d
|
|
|
3) Operating devices for inspection operation shall be provided on the top of the car. The top of car station for inspection operation, up and down, is not functioning.
|
2/7/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
1) A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program. Ref: 8.6.1.4.1(a)(1)
|
2/11/2021
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.2 Callbacks (Trouble Calls) Documentation
|
|
|
2) A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. Ref: 8.6.1.4.2
|
2/11/2021
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
4) Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load. No seal on valve. Ref: 8.6.5.16.5 Note: This Shall Be Done Next Year, during the annual inspection.
|
2/11/2021
|