Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phones must call a 24 hour monitored line that can provide, on demand, the location of the elevator. Elevator phones cannot connect to an automated messaging service. 7/5/2024
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load, within the specified limits of 3.19.4.7.5 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The Emergency Phone in the car fails to establish two-way communication.