ASME A18.1-2005 : Lifts & Chairlifts
|
11 CSR 40-5.090 Inspection and Testing
|
10 Routine, Periodic, and Acceptance inspections andTest
|
|
|
1) An auxiliary illumination source to provide general illumination of not less than 2.2 Ix (0.2 fc) on the floor and controls shall be provided. Auxililary illumination is not functioning. Ref: 10.2.2.1(d)
|
1/7/2020
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
Auxiliary lighting does not appear to work, repair same
|
7/28/2022
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
Perform Cat 5 test on safeties, last recorded Cat 5 test performed was in 2009
|
7/28/2022
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
Unit stops below top landing when operating from car, repair same so unit operates properly
|
7/28/2022
|
Missouri Minimum : Platform Lifts
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) display of certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it.
|
8/29/2024
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
The auxiliary power operation, alarm bell and emergency lighting shall operate in the absence of main power.
|
7/23/2024
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
The auxiliary power operation, alarm bell and emergency lighting shall operate in the absence of main power. Note: Not working 6/11/2024 or 7/23/2024.
|
8/29/2024
|