Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Car door restrictor shall be operational. (2nd Notice) 2/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. 12/4/2025
MO Minimum : Elevators (A) - Hoistways (A)13 Yes No Holes in hoistway shall be patched. Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height. There is an opening between the second and third landing, that opens into an occupied space. There is also an opening between the first and second landing. (2nd Notice) Re-Inspection Required 2/12/2024
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Light ray shall be overridden on Phase 1 fire service. 2/26/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Provide existing audible indicator to work upon activation of Phase 1 fire recall. Deputy Chief Gus Guadamuz has allowed 10 days of operation from 3/30/2020 for the fire service violations to be corrected. The elevator will be red tagged and locked out of service if violations are not corrected. 6/11/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Provide existing door detection system to be overridden upon activation of Phase 1 fire recall. Deputy Chief Gus Guadamuz has allowed 10 days of operation from 3/30/2020 for the fire service violations to be corrected. The elevator will be red tagged and locked out of service if violations are not corrected. 6/11/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Provide existing visual indicator to work upon activation of Phase 1 recall. Deputy Chief Gus Guadamuz has allowed 10 days of operation from 3/30/2020 for the fire service violations to be corrected. The elevator will be red tagged and locked out of service if violations are not corrected. 6/11/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No The car door restrictor shall be operational. 6/29/2021
MO Minimum : Elevators (F) - Electrical Switches (F)9 Yes No The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. (2nd Notice) Re-Inspection Required 2/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The emergency lighting shall have 2 working lamps. 6/11/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Yes No The hydraulic oil tank located in the machine room is leaking. (2nd Notice) Re-Inspection Required 2/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational on main power and battery back up. 2/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Yes No When tested, the door restrictor did not work. 2/2/2023
conversion conversion n/a No No Light Ray is not overridden on Phase I. 7/14/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 12/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/4/2025
MO Minimum : Elevators (A) - Hoistways (A)13 No No Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height. There is an opening between the second and third landing, that opens into an occupied space. There is also an opening between the first and second landing. 12/4/2025
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Oil is leaking onto the machine room floor creating a trip and fall hazard. Clean machine room floor. 7/14/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post a current state operating certificate in the elevator machine room. 7/14/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No Sight glass on tank leaking oil onto machine room floor creating a trip and fall hazard. Repair or replace as needed. 7/14/2020
MO Minimum : Elevators (F) - Electrical Switches (F)9 No No The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 12/4/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No The hydraulic oil tank located in the machine room is leaking. 12/4/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No The lighting in the machine room shall be not less than 10 foot-candles at floor level. 12/4/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 12/4/2025