Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER. 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems Yes No Hoistway door has loose guide on 2R floor. Repair/replace as needed. 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.6.2.5 Yes No Shorten Hoist Ropes. Where spring buffers are used, bottom runby shall be not less than 6". 8/31/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.6.2.5 Yes No Shorten Hoist Ropes. Where spring buffers are used, bottom runby shall be not less than 6". 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Fire Service Testing must be documented monthly. The form is present in the MCP, but hasn't been logged monthly. 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. (Expired) 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting No No Machine room lighting needs to be repaired, 1 or more bulbs not working. 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 No No Machine room door shall be self-closing and self-locking . Door does not latch. 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.1 Yes No Counterweight runby is 1". Minimum required is 6" 4/16/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No PHONE SHALL ALLOW FOR 2-WAY COMMUNICATION. 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 No No Hoist Ropes are dry and showing “rouge” and "dusting" on floor. Ropes shall be cleaned and lubricated per OEM recommendations 8/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.7 - Car door or gate 2.14.4 No No Adjust upthrust roller bearings for proper clearance to door hanger track.(all floors). 8/7/2026