Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance control program. 7/7/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Pit shall be kept clean. 7/7/2022
A17.1-1996 : Elevators 3.2 - Car top light and outlet 1001.2(c)(2) Car top GFCI has open neutral, repair as needed. 7/7/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide MCP 7/7/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) x Provide testing 7/7/2022
A17.1-1996 : Elevators 4.12 - Standby power selection switch 1002.2g Provide testing 7/7/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Emergency Power was not transferred to the elevator during testing 7/7/2022
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 202 Need to change all worn roller guides 7/18/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 5/1/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide Cat 5 testing of emergency generator and selector switch (fire control room). 8/17/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 7/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Clean car top. 7/7/2022