conversion
|
conversion
|
n/a
|
|
|
Stop switch needs to be overridden on Phase 1
|
|
conversion
|
conversion
|
n/a
|
|
|
Emergency light not working
|
|
conversion
|
conversion
|
n/a
|
|
|
The heat detector needs to be 2 ft or less from sprinkler heads
|
|
conversion
|
conversion
|
n/a
|
|
|
Seal all penetrations in the hostway
|
|
conversion
|
conversion
|
n/a
|
|
|
Pit needs to be clean and dry. Remove oil and debris
|
|
conversion
|
conversion
|
n/a
|
|
|
Sprinklers in hoistway at top. Need smoke detector and heat detectors at top of hoistway
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Top floor door closer on hoistway door is broken.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit is covered in oil. Clean
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
In car stop switch is not overridden on Phase I Fire Service when car is in flight.
|
3/19/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean oil soaked pit pads.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Overspeed valve is not sealed. Perform OSV test on or before next annual inspection.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Car stop switch not overridden on Phase I
|
4/14/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Install heat and smoke detectors at top of hoistway and less than 2 ft from sprinkler head in machine room and pit. Did not red tag.
|
4/14/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Repair hoistway penetrations in machine room around piping.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean pit.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
1. Replace broken limit switch roller at top hoistway. Rule G-1, Missouri minimum. Rule 8.11.3.1.3(F) A17.1, 2016. Rule 3.6, A17.2, 2014.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
2. Overspeed valve is not sealed and needs full load test and tripping speed checked. Rule 8.6.5.16.5, A17.1, 2016.Reinspect by 7-14-22(90 days)
|
4/14/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Repair top floor hoistway door closer. Missing Hardware
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing roller on top directional switch
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace damaged roller on car top slow down switch
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean oil soaked pads from elevator pit
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
In car stop switch shall be overridden on phase 1 fire service. Rule s-1 this violation has been written up multiple times. Repair and reinspect by 5-14-23 (30 days) or elevator wil be red tagged and removed from service
|
9/18/2024
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Elevators hoistway shall be fully enclosed to their full height
|
|