Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No Stop switch needs to be overridden on Phase 1 3/31/2026
conversion conversion n/a No No Emergency light not working 3/31/2026
conversion conversion n/a No No The heat detector needs to be 2 ft or less from sprinkler heads 3/31/2026
conversion conversion n/a No No Seal all penetrations in the hostway 3/31/2026
conversion conversion n/a No No Pit needs to be clean and dry. Remove oil and debris 3/31/2026
conversion conversion n/a No No Sprinklers in hoistway at top. Need smoke detector and heat detectors at top of hoistway 3/31/2026
MO Minimum : Elevators (A) - Hoistways (A)3 No No Top floor door closer on hoistway door is broken. 3/31/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Pit is covered in oil. Clean 3/31/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Clean oil soaked pit pads. 3/31/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No Overspeed valve is not sealed. Perform OSV test on or before next annual inspection. 3/31/2026
MO Minimum : Elevators (A) - Hoistways (A)13 No No Repair hoistway penetrations in machine room around piping. 3/31/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Clean pit. 3/31/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No 1. Replace broken limit switch roller at top hoistway. Rule G-1, Missouri minimum. Rule 8.11.3.1.3(F) A17.1, 2016. Rule 3.6, A17.2, 2014. 3/31/2026
MO Minimum : Elevators (A) - Hoistways (A)3 No No Repair top floor hoistway door closer. Missing Hardware 3/31/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace missing roller on top directional switch 3/31/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace damaged roller on car top slow down switch 3/31/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Clean oil soaked pads from elevator pit 3/31/2026
MO Minimum : Elevators (A) - Hoistways (A)13 No No Elevators hoistway shall be fully enclosed to their full height 3/31/2026
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No In car stop switch shall be overridden on phase 1 fire service. Rule s-1 this violation has been written up multiple times. Repair and reinspect by 5-14-23 (30 days) or elevator wil be red tagged and removed from service 9/18/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No 2. Overspeed valve is not sealed and needs full load test and tripping speed checked. Rule 8.6.5.16.5, A17.1, 2016.Reinspect by 7-14-22(90 days) 4/14/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Car stop switch not overridden on Phase I 4/14/2022
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Install heat and smoke detectors at top of hoistway and less than 2 ft from sprinkler head in machine room and pit. Did not red tag. 4/14/2022
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No In car stop switch is not overridden on Phase I Fire Service when car is in flight. 3/19/2020