Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)13 Repair hoistway penetrations in machine room around piping.
MO Minimum : Elevators (A) - Hoistways (A)13 Elevators hoistway shall be fully enclosed to their full height
MO Minimum : Elevators (A) - Hoistways (A)3 Repair top floor hoistway door closer. Missing Hardware
MO Minimum : Elevators (A) - Hoistways (A)3 Top floor door closer on hoistway door is broken.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 1. Replace broken limit switch roller at top hoistway. Rule G-1, Missouri minimum. Rule 8.11.3.1.3(F) A17.1, 2016. Rule 3.6, A17.2, 2014.
MO Minimum : Elevators (I) - Pits (I)1 Clean pit.
MO Minimum : Elevators (I) - Pits (I)1 Pit is covered in oil. Clean
MO Minimum : Elevators (I) - Pits (I)1 Clean oil soaked pit pads.
MO Minimum : Elevators (I) - Pits (I)1 Clean oil soaked pads from elevator pit
MO Minimum : Elevators (S) - Fire Service (S)1 x In car stop switch is not overridden on Phase I Fire Service when car is in flight. 3/19/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Install heat and smoke detectors at top of hoistway and less than 2 ft from sprinkler head in machine room and pit. Did not red tag. 4/14/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Car stop switch not overridden on Phase I 4/14/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x In car stop switch shall be overridden on phase 1 fire service. Rule s-1 this violation has been written up multiple times. Repair and reinspect by 5-14-23 (30 days) or elevator wil be red tagged and removed from service 9/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace missing roller on top directional switch
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace damaged roller on car top slow down switch
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Overspeed valve is not sealed. Perform OSV test on or before next annual inspection.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x 2. Overspeed valve is not sealed and needs full load test and tripping speed checked. Rule 8.6.5.16.5, A17.1, 2016.Reinspect by 7-14-22(90 days) 4/14/2023
conversion conversion n/a Stop switch needs to be overridden on Phase 1
conversion conversion n/a Emergency light not working
conversion conversion n/a The heat detector needs to be 2 ft or less from sprinkler heads
conversion conversion n/a Seal all penetrations in the hostway
conversion conversion n/a Pit needs to be clean and dry. Remove oil and debris
conversion conversion n/a Sprinklers in hoistway at top. Need smoke detector and heat detectors at top of hoistway