Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is inoperative. Missing building signal voltage to elevator control. 3/31/2020
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV not sealed or tagged. Perform OSV test on or before next annual inspection date. 9/6/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Need to provide wiring from disconnect for proper operation of auxiliary lowering. Re-inspection required 4/7/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating Certificate shall be displayed in elevator machine room.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Means of two way communication are inoperable and shall be repaired or replaced. 7/9/2025
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No Machine room shall be equipped with a valid fire extinguisher.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide wiring from disconnect for proper operation of auxiliary lowering 3/13/2025
conversion conversion conversion - reinspect Yes No Repair or reprogram the elevator emergency phone. 3/25/2019
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No Open splices for controller feed wiring shall be installed in the junction box