A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
204
|
|
|
2.14.1.2.3 - Handrail is missing inside the car. Equipment attached within the car enclosure shall be securely fastened.
|
7/20/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
7/20/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Annual test not complete due to packing blowing. Hoistway and fire service shall be tested.
|
10/15/2024
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Battery lowering shall work.
|
10/15/2024
|
A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(4)
|
x
|
x
|
Elevator red tagged due to blown packing during relief pressure test. Take corrective action and re-test.
|
7/11/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)10 Car Floors
|
|
|
Floor tiles are missing inside the car. All passenger elevator car floors shall be maintained so that persons are not exposed to the hazards of tripping or falling.
|
7/20/2022
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
Pit shall be clean and dry.
|
12/20/2019
|
A17.1-1996 : Elevators
|
1.3 - Operating control devices
|
1001.2(a)(3)
|
|
|
Replace missing direction arrows in return jamb.
|
1/13/2020
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
207
|
|
|
The capacity plate shall be located in a conspicuous position inside the car.
|
7/20/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational. A two-way communications means between the car and a location staffed by authorized personnel shall be provided.
|
11/3/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The state certificate is out of date.
|
7/11/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
Unit red tagged due to blown packing during relief pressure test.
|
10/15/2024
|