Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working, alarm bell ok.
MO Minimum : Elevators (I) - Pits (I)1 Oil and debris present in pit, clean. 9/30/2024
A17.1-1996 : Elevators 1.9 - Power closing of doors or gates 1001.2(a)(9) Power operation of car gate will not close gate. 5/31/2020
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room access door needs to be self-locking and non-defeatable. 5/24/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light does not operate 7/8/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Cartop light not working. 9/30/2024
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Perform overspeed valve test 1/12/2022
conversion conversion n/a Gland packing on jack leaks excessively and needs replacement. 7/23/2018
conversion conversion n/a Provide means to keep pit free of standing water. Repair sump pump, and insure water drains to sump hole. 7/23/2018
conversion conversion n/a Door unlocking pull chain boxes need to be covered and locked. 7/23/2018