Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be clean and dry, pads on floor are saturated.
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) Machine room needs proper ventilation , has floor fan to cool controller.
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) Machine room needs proper ventilation.. currently has floor fan to cool off area.
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) x Dual pistons. Both packings have been leaking Pans are overflowing and pads on pit floor saturated. Needs repack 6/17/2025
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) x Packing have been leaking pans are overflowing pads on floor are saturated, repair or replace packings as necessary.
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emeergency light and bell inoperable Bell works on normal power Needs new battery for same 6/17/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No current state operating certificate