                        A17.1-1996 : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Emergency Phone not working
                     | 
                    
                        5/7/2020
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The in car emergency phone is not working. No two-way communication.
                     | 
                    
                        11/14/2022
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        11 CSR 40-5.090 Inspection and Testing
                     | 
                    
                        (3) Testing Procedures (Re-Inspect)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Problems were encountered during the inspection and the elevator quit running. The following testing items still need to be witnessed to complete the annual inspection and category 5 test: Slide measurement shall be obtained, the pressure switch shall be tested, low oil switch shall be tested, Phase 1 & 2 fire service shall be tested, emergency phone & lighting shall be tested, and door closing force shall be tested.
                     | 
                    
                        3/26/2021
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        2.41 - Maintenance Records
                     | 
                    
                        8.6.1.4
                     | 
                    
                     | 
                    
                     | 
                    
                        A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        2.7 - Fire Extinguisher
                     | 
                    
                        1206.1h
                     | 
                    
                     | 
                    
                     | 
                    
                        A current ABC type fire extinguisher shall be provided in the machine room.
                     | 
                    
                        10/10/2025
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        2.7 - Fire Extinguisher
                     | 
                    
                        1206.1h
                     | 
                    
                     | 
                    
                     | 
                    
                        A current ABC type fire extinguisher shall be provided in the machine room.
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        CSR  40-5.100 State Operating Certificate
                     | 
                    
                        5.100(2) Display of Operating Certificate
                     | 
                    
                     | 
                    
                     | 
                    
                        A current state operating certificate shall be displayed in the machine room in a non-combustible frame.
                     | 
                    
                        
                     |