A17.1-1996 : Elevators
|
2.17 - Drive machine brake
|
1001.2(b)(15)
|
x
|
x
|
The drive machine brake will not lower and hold a car load of 125% of the rated capacity. Repair and reinspection required.
|
5/28/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed.
|
5/28/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time, only the red tagged item has been corrected. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed.
|
6/28/2021
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
x
|
|
Without proper permanent ventilation, the machine room temperature is causing damage to the controller and motor. A permanent ventilation system shall be installed to prevent further damage.
|
7/15/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
Thermostatic control on the drive machine shall be repaired back to normal operation to ensure that the proper safety precautions take place in a possible event of excessive temperatures.
|
7/15/2024
|