MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Close holes in hoist way around conduit
|
9/11/2024
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Close holes in hoistway around conduit
|
9/11/2024
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Close holes in hoistway around conduit
|
9/11/2024
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Close holes in hoistway around conduit
|
9/11/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone is not working with 110 volt disconnect off. Re-inspection required
|
11/7/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Ceiling panels in car are open egg crate type. Providing no protection for passengers in event of light bulb breakage. Replace with solid type panels or install plastic tubes and end caps on bulbs.
|
9/11/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Ceiling panels in car are open crate type which provides no protection for passengers in event of light bulb breakage. Replace panels with solid type or install plastic tubes and end-caps over bulbs
|
9/11/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Remove temporary wiring to exhaust fan and replace with proper wiring to NFPA 70
|
9/11/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room shall not be used for storage
|
9/11/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Remove temporary wiring to exhaust fan and replace with proper wiring to NFPA 70
|
9/11/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Remove temporary wiring to exhaust fan and replace with proper wiring to NFPA 70
|
9/11/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Remove tempoary wiring to exhaust fan and replace with proper wiring to NFPA 70
|
9/11/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean oil from pit
|
9/11/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Need to clean oil from pit
|
9/11/2024
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Machine room shall not be used for storage.
|
9/11/2024
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
1001.2(b)(6)
|
|
|
Repair ventilation fan in machine room.
|
9/11/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display operating certificate in machine room.
|
9/11/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be on display in machine room
|
9/11/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be on display in the machine room
|
9/11/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
9/11/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated Missouri Operating Certificate in machine room
|
9/11/2024
|