Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022) 2/28/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/29/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency bell and phone shall work. 10/16/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car emergency lights shall work. 1/2/2019
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Provide code compliant machine room lighting. The illumination the machine room shall be not less than 10 foot-candles at the floor level.
MO Minimum : Elevators (H) - Machine Rooms (H)1 Provide safe and convenient access to the elevator machine room. Wooden stairs leading to machine room are worn and unsafe. 2/28/2022
MO Minimum : Elevators (I) - Pits (I)1 Remove fluids from the pit. The pit shall be kept dry. 2/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Remove the bag covering the smoke detector in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The car safety edge re-opening device does not work properly when car door is a foot from fully closing. 8/17/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The doors stopped working during the inspection. All category 5 and annual inspection items have been completed with the exception of fire service. Fire service shall be tested as part of the category 5 annual inspection 10/8/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency lighting shall be operational. 8/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 10/4/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency telephone shall be operational. 8/17/2022
MO Minimum : Elevators (I) - Pits (I)1 The pit sump pump shall work. 2/28/2022