Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car emergency light shall work. 1/2/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency bell and phone shall work. 10/16/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The existing machine room air conditioner (window unit) shall be repaired or replaced. 2/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The photo eyes for the door re-opening device shall be operational. (The mechanical safety edge is operational) 10/8/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency lighting shall be operational. 10/8/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The photo eyes for the door re-opening device shall be operational. (The mechanical safety edge is operational) 8/26/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door restrictor is missing. 1/19/2023
MO Minimum : Elevators (I) - Pits (I)1 Remove water from pit floor and clean pit.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x The Phase 1 visual signal shall be operational at the fire service key switch. 1/19/2023
A17.1-2016 : Elevators 2.1 - Access to machine space 8.10.2.2.2(d) x The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. 11/15/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) x A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 11/15/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(d)(1) x Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 11/15/2022
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.10.2.2.4(b) x The basement floor has an iron gate attached to the door frame. A key is required to open this gate, thus restricting a person from exiting the elevator at that floor. If the elevator was to fall and get stuck at that floor a person or persons would be entrapped. This is a safety hazard, remove the gate. Doors shall not lock any landing opening in the hoistway enclosure from the hoistway side nor lock any exit leading from any hoistway landing to outside of the building. 11/15/2022
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate x Post a current MO state operating certificate. 11/15/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.