A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean pit.
|
8/26/2021
|
A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
1001.2(a)(12)
|
|
|
Handrail in car is missing. Replace.
|
8/26/2021
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Sump pump may not be working. Hole is filled with liquid. Repair.
|
8/26/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Phase II operations are worn and not legible. Replace.
|
8/26/2021
|
A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(4)
|
|
|
Cylinder packing worn and leaking, repair as needed.
|
8/26/2021
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Clean pit, sump pump is full and not working.
|
10/21/2021
|
A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
1001.2(a)(12)
|
|
|
Handrail in car is missing. Replace
|
10/21/2021
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV in pit not sealed. Test, tag and seal upon completion.
|
4/15/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone is not working correctly, low voltage.
|
10/2/2023
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Clean the pit(fluids).
|
10/3/2023
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Sump hole is filled with liquid (s), remove.
|
10/3/2023
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Determine if the sump pump is working correctly, if not then replace.
|