Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Clean pit. 8/26/2021
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) No No Handrail in car is missing. Replace. 8/26/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Sump pump may not be working. Hole is filled with liquid. Repair. 8/26/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No Phase II operations are worn and not legible. Replace. 8/26/2021
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) No No Cylinder packing worn and leaking, repair as needed. 8/26/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Clean the pit(fluids). 10/3/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Sump hole is filled with liquid (s), remove. 10/3/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Determine if the sump pump is working correctly, if not then replace. 10/3/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Clean pit, sump pump is full and not working. 10/21/2021
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) No No Handrail in car is missing. Replace 10/21/2021
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No OSV in pit not sealed. Test, tag and seal upon completion. 4/15/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Phone is not working correctly, low voltage. 10/2/2023