Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Car emergency lighting not workingg
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevator has emergency power however unable to engage for test. 8/24/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevator failed to sequence down and operate properly during emergency power test. 12/18/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In-car two way communication not working. 10/20/2025
conversion conversion n/a MACHINE ROOM LIGHTS DO NOT PRODUCE ENOUGH LIGHT AT THE CONTROLLER. BULBS ARE OUT. 10/15/2018