Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | Elevator has emergency power however unable to engage for test. | 8/24/2021 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | Elevator failed to sequence down and operate properly during emergency power test. | 12/18/2021 | |
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | Machine room lighting do not produce 10ftc at controller. Bulbs are out. | 10/1/2018 |