A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
|
|
Per NEC, repair disconnect and replace 4x4 box cover.
|
11/4/2020
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
Disconnect is rusting out due to water damage.
|
11/4/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated certificate in machine room.
|
11/4/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certificate in machine room
|
11/4/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Need maintenance control program on site posted on controller
|
11/4/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Need fire service log posted in machine room to be tested monthly
|
11/4/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Water damage on electric disconnects in machine room
|
11/4/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(b)(2) Hydraulic elevators Placed out of Service
|
x
|
x
|
Severe water damage.
|
7/12/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit lighting is not working, needs to be repaired
|
11/7/2023
|
A17.1-1996 : Elevators
|
1.14 - Ventilation
|
204.3c
|
x
|
|
Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required
|
10/10/2024
|