Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Per NEC, repair disconnect and replace 4x4 box cover. 11/4/2020
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 Disconnect is rusting out due to water damage. 11/4/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated certificate in machine room. 11/4/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 11/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need maintenance control program on site posted on controller 11/4/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Need fire service log posted in machine room to be tested monthly 11/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Water damage on electric disconnects in machine room 11/4/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit lighting is not working, needs to be repaired 11/7/2023
A17.1-1996 : Elevators 1.14 - Ventilation 204.3c x Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required 10/10/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service x x Severe water damage. 7/12/2023