Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 x Stop switch not working. 7/23/2019
A17.1-1996 : Elevators 1.14 - Ventilation 204.3c Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x x OSV test performed, elevator would not level at top landing and kept hitting stop ring. Red tagged elevator. 7/28/2021
conversion conversion n/a Post current State certificate in machine room 11/4/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work, needs repair. Re-inspection required 7/12/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service x x Severe water damage. 7/12/2023
MO Minimum : Elevators (I) - Pits (I)1 Need to clean oil from elevator pit. 11/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance x Cylinder head on hydraulic jack has leaking packing seal, need to replace seal. Re-inspection required 10/26/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post State certificate in machine room 11/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need maintenance conttrol program on site posted on controller 11/4/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Need fire service log posted in machine room to be be tested monthly 11/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Water damage on electric disconnects in machine room 11/4/2020