Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 1206.8 x Provide code compliant minimum counterweight runby. 5/22/2024
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 205.15 x x Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the pull-through force was overly excessive and could potentially permanently damage the elevator safeties if testing proceeded. The elevator has been removed from service. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service.
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 206 x x The safety governor rope was worn into the governor sheave and shall be replaced.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 test is incomplete, need to perform the following tests to complete inspection: 125% brake test, set safeties with capacity load, car & counterweight buffer test, pull out, pull thru test, governor overspeed switch and jaws spin test need to be performed and completed. Re-inspection required.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 test is incomplete, need to perform the following tests to complete inspection: 125% brake test, set safeties with capacity load, car & counterweight buffer test, pull out, pull thru test, governor overspeed switch and jaws spin test need to be performed and completed. Re-inspection required 6/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean car top.