A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.4.19.13 Broken Suspension Member and Residual Strength Detection Means
|
x
|
|
Belt monitor for the hoist belts is flashing an error on the new hoist belts that were installed, repair belt monitor
|
12/19/2024
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
coated steel belt monitor is flashing an error, test the belts, if good reset the monitor, if bad replace the hoist belts (8.6.3.2.3)
|
11/8/2023
|
A17.1-1996 : Elevators
|
3.26 - Broken rope, chain, or tape switch
|
209.2c(2)
|
x
|
|
Coated steel belt monitor is showing errors on several belts, repair belt monitor
|
11/2/2020
|
A17.1-2016 : Elevators
|
3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.6.4.19.17 Earthquake Operation
|
x
|
|
could not get the seismic to trip, repair and retest (8.6.4.19.17)
|
11/8/2023
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
machine room fire extinguisher does not have an inspection tag, have the extinguisher inspected and tagged annually
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(j)
|
|
|
machine room fire extinguisher is to be inspected and tagged annually
|
1/20/2021
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
perform and post monthly fire service test log in the elevator machine room
|
1/20/2021
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Provide machine room fire extinguisher
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate in the machine room expired in 2011, update with current state operating certificate when received
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.11.2.1.3(cc)
|
x
|
|
The coated steel belt monitor is flashing an error, repair/reset the belt monitor verify that the belts test good
|
11/14/2022
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the copy of the state operating certificate in the machine room is to be updated annually
|
1/20/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone is not working.
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection)
|
|
|
the fire hat light in the car operating panel did not come on during the fire service test
|
1/20/2021
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.11.2.1.3(cc)
|
|
|
the hoist belt monitor is showing an error, the belts tested good, replace faulty belt monitor
|
1/20/2021
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
the junction box and conduit for the pit stop switch, buffer switch, tail sheave switch is rusted in half and wires are exposed in a couple of places, replace rusted out conduit and junction box (2.8.2.1)
|
|
A17.1-2016 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.11.2.1.2(nn)
|
|
|
tried to trip the seismic and it would not trip, repair and retest
|
|