Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written maintenance control program shall be kept on site 1/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone shall provide 2 way communication 8/23/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall provide 2 way communication. Re-inspection required 1/18/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Provide testing of rupture valve in pit. 11/29/2022
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Provide machine room door to be self locking type. 11/29/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide fire log and oil loss log. 11/29/2022
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) Remove scavenger line from jack that goes all the way back to tank. Seal fittings as needed. 1/18/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room 1/18/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate shall be properly displayed in machine room 1/18/2023