A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.7.2.25
|
|
|
no rope grippers installed with new machines
|
2/25/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
no maint records on site
|
5/18/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
|
|
couldnt run emg. power test at time of insp
|
2/25/2021
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
8.7.2.9
|
|
|
no report from licensed professional eng.on support for new floor an mach. beams.
|
5/18/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
|
|
standby power test didnt work properly
|
2/25/2021
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.7.2.25.1
|
|
|
no rope gripper or emg. brake
|
2/25/2021
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
no mcp on site
|
5/18/2023
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
8.7.2.9
|
|
|
no report on mach. room floor by prof eng.
|
5/18/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt
|
5/18/2023
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
8.7.2.9
|
|
|
no report on mach. room floor by prof. eng.
|
5/18/2023
|
A17.1-2016 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
|
|
plateform guards need to be 48 ins deep with emg brake
|
5/18/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt. displayed
|
5/18/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt displayed
|
9/16/2024
|
A17.1-2016 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
|
|
need to have 48 in. platform guard or variance
|
9/16/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.5.14.3(f)
|
x
|
|
emg power couldnt be tested at time of insp
|
3/6/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emg phone keeps dropping call
|
5/9/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
emg power couldnt be tested at this time scheduled for april
|
2/27/2023
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.7.2.25.1
|
x
|
|
no emg.brake installed
|
2/27/2023
|