MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
no records of any kind on site
|
2/27/2023
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.7.2.25.1
|
|
|
new mach no rope gripper
|
2/25/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
|
|
couldnt run emg. power test at time of insp.
|
2/25/2021
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
8.7.2.9
|
|
|
no report from licensed prof. eng.on support for new floor an mach. beams
|
2/27/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
|
|
standby power didnt work properly
|
2/25/2021
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.7.2.25.1
|
|
|
no rope gripper or emg. brake
|
2/25/2021
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
no mcp on site
|
2/27/2023
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
8.7.2.9
|
|
|
no report on mach.room floor over hoistway by prof. eng.
|
2/27/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt. displayed
|
6/24/2024
|
A17.1-2016 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
|
|
platform guards need to be 48 ins. with emg brake
|
6/12/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
current operatig cirt not displayed
|
3/6/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt displayed
|
6/24/2024
|
A17.1-2016 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
|
|
need to have a 48 in platform guard or a variance
|
6/12/2024
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
8.7.2.9
|
|
|
no eng. study done on mach. room floor done by prof. eng.
|
6/24/2024
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.7.2.25.1
|
x
|
|
no emg. brake installed as per code
|
2/27/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.5.14.3(f)
|
x
|
|
couldnt run emg power test at time of insp
|
3/6/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emg power couldnt be tested at this time scheduled for april
|
2/27/2023
|