Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records no maint records on site 2/27/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x couldnt test emg power at time of insp. 7/8/2020
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.7.2.25.1 no rope gripper on nwe machine 2/25/2021
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.7.2.9 no report from lic. pro. eng. onsupport for new mach. room floor an mach. beams 2/27/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) standby power test didnt work properly 2/25/2021
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.7.2.25 no rope gripper or emg. brake 2/25/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) no mcp on site 2/27/2023
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.7.2.9 no report on mach. room floor over hoistway by prof. eng. 9/16/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. displayed 9/16/2024
A17.1-2016 : Elevators 4.1 - Car platform guard 2.15.9 platform guard less than 48 ins. 9/16/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. displayed 9/16/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt displayed 9/16/2024
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.7.2.9 no eng. report on mach. room floor by prof. eng. 9/16/2024
A17.1-2016 : Elevators 4.1 - Car platform guard 2.15.9 need to have 48 in platform guard or a variance 9/16/2024
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 102.1 damaged traveling cable exposed wires 9/16/2024
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.7.2.25.1 x no emg brake installed as per code 2/27/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x emg power couldnt be tested at time of insp 3/6/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x test couldnt be done at this time scheduled for april 2/27/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 x x couldnt test fire int. devices in overhead or 8th floor 2/26/2019