A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
|
x
|
couldnt test emg power at time of insp.
|
7/8/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
x
|
couldnt test fire int. devices in overhead or 8th floor
|
2/26/2019
|
A17.1-1996 : Elevators
|
3.16 - Traveling cables and junction boxes
|
102.1
|
|
|
damaged traveling cable exposed wires
|
9/16/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.5.14.3(f)
|
x
|
|
emg power couldnt be tested at time of insp
|
3/6/2024
|
A17.1-2016 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
|
|
need to have 48 in platform guard or a variance
|
9/16/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt displayed
|
9/16/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt. displayed
|
9/16/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt. displayed
|
9/16/2024
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.7.2.25.1
|
x
|
|
no emg brake installed as per code
|
2/27/2023
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
8.7.2.9
|
|
|
no eng. report on mach. room floor by prof. eng.
|
9/16/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
no maint records on site
|
2/27/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
no mcp on site
|
2/27/2023
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
8.7.2.9
|
|
|
no report from lic. pro. eng. onsupport for new mach. room floor an mach. beams
|
2/27/2023
|
A17.1-2016 : Elevators
|
2.16 - Overhead Beam and Fastenings
|
8.7.2.9
|
|
|
no report on mach. room floor over hoistway by prof. eng.
|
9/16/2024
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.7.2.25.1
|
|
|
no rope gripper on nwe machine
|
2/25/2021
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.7.2.25
|
|
|
no rope gripper or emg. brake
|
2/25/2021
|
A17.1-2016 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
|
|
platform guard less than 48 ins.
|
9/16/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
|
|
standby power test didnt work properly
|
2/25/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
test couldnt be done at this time scheduled for april
|
2/27/2023
|