Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.1 - Car platform guard 2.15.9 platform guard less than 48 ins. 9/16/2024
A17.1-2016 : Elevators 4.1 - Car platform guard 2.15.9 platform guard needs to be 48 ins or have a variance 9/16/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt displayed 9/16/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt displayed 9/16/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. displayed 9/16/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) no mcp on site 2/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records no maint records on site 2/29/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) emg power couldnt be tested at time of insp 2/25/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) standby power test didnt work properly 2/25/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x test couldnt be done at this time scheduled for april 2/29/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x emg power couldnt be tested at time of insp 3/6/2024
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.7.2.25 x emg. brake not installed as per code 2/29/2024
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.7.2.25.1 no rope gripper or emg. brake 2/25/2021
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.7.2.25.1 no rope gripper but new mach. 2/25/2021
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.7.2.9 no report from lic. pro. eng. on support for new floor an mach.room beams 9/16/2024
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.7.2.9 no report by prof. eng. on machine room floor over hoistway 9/16/2024
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.7.2.9 no report on mach room floor by prof. eng. 9/16/2024