Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records no records on site
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.7.2.9 no report from lic. prof. eng. on support for new floor an mach. beams
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.7.2.9 no report on mach. room floor by prof. eng.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) no mcp on site
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) standby power test didnt work properly 2/25/2021
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.7.2.25.1 no rope gripper or emg. brake 2/25/2021
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.7.2.25 new mach. no rope gripper 2/25/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) couldnt test emg power at time of insp 2/25/2021
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.7.2.25.1 x emg. brake was not installed as per code 2/27/2023
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake x unintended motion failed 2/27/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x couldnt test at this time scheduled for april 2/27/2023
A17.1-2016 : Elevators 4.1 - Car platform guard 2.15.9 platform guard needs to be 48ins. with emg. brake 6/12/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. displayed 6/24/2024
A17.1-2016 : Elevators 2.16 - Overhead Beam and Fastenings 8.7.2.9 no report on mach.room floor over hoistway by prof. eng. 6/24/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. on display 6/24/2024