ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2 way communications device shall be operational.
|
5/6/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Seal penetrations in hoistway around hoistway door frames and fire caulk seam where hoistway walls meet top of pit wall.
|
5/6/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
x
|
|
Collection of oil leakage; need containers with lids, not to exceed 5 gallon capacity in pit to collect leakage from each jack.
|
5/6/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
Fire alarm initiating devices and fire panel not functioning. Unit will not respond if there is a fire in the building. Elevator RED TAGGED.
|
5/6/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Rail bracket on pit floor next to sump pump is extremely rusted and has lost structural integrity. The bracket shall be replaced.
|
5/6/2025
|