Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Fire alarm initiating devices and fire panel not functioning. Unit will not respond if there is a fire in the building. Elevator RED TAGGED. 5/6/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communications device shall be operational. 5/6/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Seal penetrations in hoistway around hoistway door frames and fire caulk seam where hoistway walls meet top of pit wall. 5/6/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Rail bracket on pit floor next to sump pump is extremely rusted and has lost structural integrity. The bracket shall be replaced. 5/6/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection x Collection of oil leakage; need containers with lids, not to exceed 5 gallon capacity in pit to collect leakage from each jack. 5/6/2025