Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes Yes Fire alarm initiating devices and fire panel not functioning. Unit will not respond if there is a fire in the building. Elevator RED TAGGED. 5/6/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Rail bracket on pit floor next to sump pump is extremely rusted and has lost structural integrity. The bracket shall be replaced. 5/6/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Yes No Seal penetrations in hoistway around hoistway door frames and fire caulk seam where hoistway walls meet top of pit wall. 5/6/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No 2 way communications device shall be operational. 5/6/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Yes No Collection of oil leakage; need containers with lids, not to exceed 5 gallon capacity in pit to collect leakage from each jack. 5/6/2025