Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)1 Remove portable air conditioner from machine room in order to allow proper access and working clearance requirements
MO Minimum : Elevators (I) - Pits (I)1 Pit floor covered in oil
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal No audible signal during fire recall operation. 12/22/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate state operating certificate not displayed
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. displayed
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x battery lowering failed