Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Pit oil reservoir overflowing 10/21/2024
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No OSV is not sealed. Perform OSV test within 90 days. 6/9/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Failed Cat 1 standby power test. Re-inspection required 10/21/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No No maintenance records on site. 7/8/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Provide testing of battery backup lowering unit. 1/13/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Battery Backup not working 4/28/2026