Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 4x4 junction box behind the governor on the hoistway wall is missing it's cover
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a new copy of the state operating certificate is to be posted in the machine room every year
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) belt monitor is flashing an error on the center belt, if the belt tests good repair the belt monitor, otherwise replace the belts 2/24/2023
A17.1-1996 : Elevators 3.26 - Broken rope, chain, or tape switch 210.2(f) x belt monitor is flashing error on belt 3, hoist belts are roughed, belt monitor has been bypassed alowing the elevator to run. repair the belt monitor and clean the rouge off of the belts 10/19/2020
conversion conversion conversion - reinspect x coated steel belt monitor is flashing error that says it is time to replace the belts 7/27/2018
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 machine room maintenance logs have not been filled out since 2017, fill out log for every visit, callback, and maintenance
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 monthly fire service test log has not been filled out
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) monthly fire service test log has not been filled out monthly, test fire service monthly and fill out the log in the machine room
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits pit light is burnt out, replace light bulb
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 pit light is burnt out, replace pit light bulb
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) post monthly fire service test log in the machine room
A17.1-1996 : Elevators 3.11 - Hoistway smoke control 100.4 the smoke damper at the top of the hoistway is fully open, which means the damper motor has failed or the the damper motor has lost power, repair smoke damper
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 8.11.2.1.3(q) the smoke damper at the top of the hoistway is open, which means the damper motor has failed or that the damper motor has lost power.
A17.1-1996 : Elevators 3.11 - Hoistway smoke control 100.4 the smoke damper at the top of the hoistway is open, which means the damper motor has failed or the the damper motor has lost power, should only open to prevent the accumulation of smoke and hot gases
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) the sprinkler head at the top of the hoistway is not connected to a water supply line, it is just a pipe that goes through the wall
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 the sprinkler line Projecting 3 feet into the hoistway is not hooked up to the building water supply, either apply for a variance to remove or repair and hook back up to the water supply
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state annually
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate posted in the machine room expired in 2011, update with current copy when received from the state of Missouri
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 top of hoistway sprinkler line is not hooked up to the sprinkler supply line, it has been disconnected outside of the hoistway, elevator is equipped with belts that are not fire rated
conversion conversion n/a top of hoistway sprinkler line is not hooked up to the sprinkler system, it has been disconnected but the line into the hoistway is still there