Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.2.1.5(a) replace burnt out pit light bulb
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 monthly fire service test log is to be filled out and posted in the machine room
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a new copy of the state operating certificate is to be posted in the machine room when they come in every year
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state annually
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) monthly fire service test log has not been filled out monthly, test fire service monthly and fill out the log in the machine room
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 machine room maintenance logs have not been filled out since 2017, fill out the log in the machine room for every visit, callback, and maintenance
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate posted in the machine room expired in 2011, update the state operating certificate posted in the machine room with the current copy when received from the state of Missouri
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 monthly fire service test log has not been filled out monthly
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting all of the machine room lights are burnt out, repair or replace lights
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Remove older permit and provide updated one in a displayable location
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Owner to keep updated monthly fire service log
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Repair remote governor reset solenoid - 2.7.6.5 means necessary for testing
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Repair/re-lamp pit light
MO Minimum : Elevators (I) - Pits (I)1 Keep pit free of dust and debris
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean the car top
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Provide proper counterweight runby - remove stinger
conversion conversion n/a governor tail sheave switch arm is not between the pins on the tail sheave
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x the emergency phone did not work 2/24/2023