Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a both of the kellum grips that hold the traveling cables have broken and need replaced
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state annually
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation monthly fire service test log in the machine room has not been filled out monthly, test fire service monthly and fill out the log in the machine room
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 machine room maintenance logs have not been filled out since 2017, fill out maintenance log for every callback and maintenance visit
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state of Missouri annually
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 monthly fire service test log has not been filled out monthly, test fire service monthly and fill out log in the machine room
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting replace burnt out machine room lights, all of the lights are not working in the machine room
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Remove old permit with updated one in a displayable location
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Owner to keep monthly fire service log updated
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Keep pits free of dust and debris
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Top of Cars Clean the car top
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) x Provide proper counterweight runby - remove stinger
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone is functioning however due to static the operator has difficulty hearing
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.19.3 x Repair remote governor reset - 2.7.6.5 provide means for testing