Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Repair phone speaker - security cannot hear occupant, repeat 9/2/2025 reinspection required within 15 days
MO Minimum : Elevators (I) - Pits (I)1 No No Clean debris from the pit
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No replace burnt out machine room lights, all of the lights are not working in the machine room 11/23/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Phone is functioning however due to static the operator has difficulty hearing 9/2/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state annually, repeat 9/2/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No the state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state of Missouri annually 11/23/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Remove old permit with updated one in a displayable location 11/23/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No the state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state annually 11/23/2025
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No machine room maintenance logs have not been filled out since 2017, fill out maintenance log for every callback and maintenance visit 11/23/2025
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No monthly fire service test log has not been filled out monthly, test fire service monthly and fill out log in the machine room 11/23/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation No No Monthly fire service test log has not been filled out monthly, test fire service monthly and fill out log in the machine room; repeat violation 8/26/2024, repeat 9/2/2025 and update PM logs
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No monthly fire service test log in the machine room has not been filled out monthly, test fire service monthly and fill out the log in the machine room 11/23/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Owner to keep monthly fire service log updated 11/23/2025
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) Yes No Provide proper counterweight runby - remove stinger 9/2/2025
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.19.3 Yes No Repair remote governor reset - 2.7.6.5 provide means for testing 11/23/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Keep pits free of dust and debris
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Top of Cars No No Clean the car top
conversion conversion n/a No No both of the kellum grips that hold the traveling cables have broken and need replaced 11/23/2025