MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-locking and self-closing.
|
6/26/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-locking and self-closing.
|
5/28/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
2/8/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it.
|
2/8/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
Up-to-date wiring diagrams shall be provided and permanently kept in the machine room.
|
2/8/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
5/28/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Muffler has slight leak. Monitor the status and take corrective action as needed.
|
5/1/2024
|