Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove all non elevator storage from the machine room 10/3/2024
MO Minimum : Elevators (I) - Pits (I)1 Clean drip pans in the pit & provide covers 10/3/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 10/3/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test & document on log in machine room 10/3/2024
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 10/3/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) Empty drip pans in the pit & provide covers 10/3/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(d) Provide complete maintenance control program and post on controller 10/3/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Perform monthly fire service test & document on log in machine room 10/3/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for fire fighters' service operations, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation and the date shall be available on-site.
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 x Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from it's load when the disconnecting means is in the open position. Note: A jumper exists from terminal Aux to APE relay contact 32 where the auxiliary contact above should be connected. The additional power source (UPS) should not be functioning until the contact in the disconnect is provided and working. With a jumper in place of the auxiliary contact above and working UPS installed, the elevator could come down on emergency lowering with the main disconnect in the off position, which could present a safety hazard for personnel working on the elevator.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The auxiliary power lowering operation shall be functional. Note: The UPS will not stay on.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/8/2024